Retail Sales Price: Panasonic Online Price: SHOP NOW SHOP NOW WHERE TO BUY Buy from Panasonic Where to Buy Out of Stock at Panasonic Online false false false

E2 Type High Static Ducted/High Fresh Air Ducted

Add to WishlistRemove from Wishlist

NO ROOM TO ADD MORE PRODUCTS

The wishlist has already reached the maximum number of products

E2 Type High Static Ducted/High Fresh Air Ducted

High static and large airflow ducted with fresh air intake

E2 Type High Static Ducted/High Fresh Air Ducted units offer improved design flexibility in extended duct layouts thanks to their increased external static pressure. They also provide 100% fresh air intake for ventilation (except for S-180ME2E5).
  • R410A
  • High Fresh Air
Zoom In
Zoom Out
Close
E2 Type High Static Ducted/High Fresh Air Ducted

Specs

S-180ME2E5

Photo of S-180ME2E5

S-224ME2E5

Photo of S-224ME2E5

S-280ME2E5

Photo of S-280ME2E5
  • R410AR410A
  • High Fresh AirHigh Fresh Air
  • DC motorDC motor

Design flexibility thanks to high static pressure and large air volume

Power input 45% less (High Static Ducted type, compared to E1 type)

Power input 45% less (High Fresh Air Ducted type, compared to H1 type)

Discharge air temperature control to reduce cold drafts during heating operation

Configurable air temperature control

100% fresh air intake for ventilation purposes (except for S-180ME2E5)

S-180ME2E5 S-224ME2E5 S-280ME2E5
Power Source (50 Hz) 220/230/240 V, 1 phase 220/230/240 V, 1 phase 220/230/240 V, 1 phase
Power Source (60 Hz) 220/230 V, 1 phase 220/230 V, 1 phase 220/230 V, 1 phase
Cooling Capacity 18.0 kW, 61,400 Btu/h 22.4 kW, 76,400 Btu/h 28.0 kW, 95,500 Btu/h
Heating Capacity 20.0 kW, 68,200 Btu/h 25.0 kW, 85,300 Btu/h 31.5 kW, 107,500 Btu/h
Power Input (Cooling) 0.400 kW 0.440 kW 0.715 kW
Power Input (Heating) 0.400 kW 0.440 kW 0.715 kW
Running Current (Cooling) 2.40/2.30/2.20 A 2.55/2.45/2.35 A 3.95/3.85/3.70 A
Running Current (Heating) 2.40/2.30/2.20 A 2.55/2.45/2.35 A 3.95/3.85/3.70 A
Fan Type Sirocco Fan Sirocco Fan Sirocco Fan
Air Flow Rate (H/M/L) 2,940/2,640/2,340 m³/h, 817/733/650 L/s 3,360/3,060/2,640 m³/h, 933/850/733 L/s 4,320/3,780/3,180 m³/h, 1,200/1,050/883 L/s
Fan Motor Output 0.560 x 2 kW 0.560 x 2 kW 0.750 x 2 kW
External Static Pressure 140 Pa 140 Pa 140 Pa
Sound Power Level (H/M/L) 76/74/72 dB 77/75/73 dB 81/79/75 dB
Sound Pressure Level (H/M/L) 44/42/40 dB (A) 45/43/41 dB (A) 49/47/43 dB (A)
Dimension H479 x W1,453 x D1,205 mm H479 x W1,453 x D1,205 mm H479 x W1,453 x D1,205 mm
Pipe Connection (Liquid) Ø9.52 mm (Ø3/8 inch) Ø9.52 mm (Ø3/8 inch) Ø9.52 mm (Ø3/8 inch)
Pipe Connection (Gas) Ø19.05 mm (Ø3/4 inch) Ø19.05 mm (Ø3/4 inch) Ø22.22 mm (Ø7/8 inch)
Pipe Connection (Drain Piping) VP-25 VP-25 VP-25
Net Weight 102 kg 102 kg 106 kg
Fresh Air: Power Source (50 Hz) - 220/230/240 V, 1 phase 220/230/240 V, 1 phase
Fresh Air: Power Source (60 Hz) - 220/230 V, 1 phase 220/230 V, 1 phase
Fresh Air: Cooling Capacity - 22.4 kW, 76,400 Btu/h 28.0 kW, 95,500 Btu/h
Fresh Air: Heating Capacity - 21.2 kW, 72,300 Btu/h 26.5 kW, 90,400 Btu/h
Fresh Air: Power Input (Cooling) - 0.290 kW 0.350 kW
Fresh Air: Power Input (Heating) - 0.290 kW 0.350 kW
Fresh Air: Running Current (Cooling) - 1.90/1.85/1.80 A 2.30/2.20/2.10 A
Fresh Air: Running Current (Heating) - 1.90/1.85/1.80 A 2.30/2.20/2.10 A
Fresh Air: Fan Type - Sirocco Fan Sirocco Fan
Fresh Air: Air Flow Rate (H/M/L) - 1,700 m³/h, 472 L/s 2,100 m³/h, 583 L/s
Fresh Air: Fan Motor Output - 0.560 x 2 kW 0.750 x 2 kW
Fresh Air: External Static Pressure - 200 Pa 200 Pa
Fresh Air: Sound Power Level (H/M/L) - 75 dB 76 dB
Fresh Air: Sound Pressure Level (H/M/L) - 43 dB (A) 44 dB (A)
Fresh Air: Dimension - H479 x W1,453 x D1,205 mm H479 x W1,453 x D1,205 mm
Fresh Air: Pipe Connection (Liquid) - Ø9.52 mm (Ø3/8 inch) Ø9.52 mm (Ø3/8 inch)
Fresh Air: Pipe Connection (Gas) - Ø19.05 mm (Ø3/4 inch) Ø22.22 mm (Ø7/8 inch)
Fresh Air: Pipe Connection (Drain Piping) - VP-25 VP-25
Fresh Air: Net Weight - 102 kg 106 kg

Documents

Combination

Case Studies

Features

Cooling/Heating kW (rated)

18.0/20.0

22.4/25.0

28.0/31.5

Cooling/Heating Btu/h (rated)

61,400/68,200

76,400/85,300

95,500/107,500

Model No.

S-180ME2E5*

S-224ME2E5

S-280ME2E5

*This model is not equipped with high fresh system.

Fresh Air Intake Possible

High Fresh System enables the delivery of fresh outside air at almost the same temperature and humidity as indoor air without putting a burden on air conditioning.
Note: Only S-224ME2E5, S-280ME2E2E5. Capable of treating outdoor air only. Indoor air conditioner units are required to adjust indoor air temperature.
Fresh Air Intake Possible

Mix Operation Unit with Standard Indoor Units

Possible to combine high fresh air ducted indoor units and standard air ducted indoor units. When other indoor units are connected in the same circuit, keep the following capacity ratio. E2 type / outdoor unit < 30%, and total of indoors (incl. E2) / outdoor < 100%
Mix Operation Unit with Standard Indoor Units

Selectable Static Pressure for Installation Flexibility

3-Step Static Pressure Set Up

You can select between the three static pressure modes of 270 Pa /140 Pa / 60 Pa (72 Pa*) for extra installation flexibility.
Note: Only the High Static Ducted type. *28 kW model
3-Step Static Pressure Set Up

Max. 270 Pa Static Pressure Setting for Large Facilities

A maximum static pressure setting of a high 270 Pa enables the use of long ducts for installation in a wide range of spaces. Ideal for large-scale offices, restaurants, and other facilities.
Max. 270 Pa Static Pressure Setting for Large Facilities

Installation of Inspection Port Necessary

An inspection port (600 x 600 mm or more) is required at the lower side of the indoor unit body (field supply).
Installation of Inspection Port Necessary

Leading Control Options

Panasonic air conditioning systems allow flexible control options. Individual, centralised, Cloud control and WLAN control are all possible. Please consult with a Panasonic air conditioning specialist for advice as to which control solution best suits your system requirements.
Leading Control Options

Optional Parts for High Static Ducted Series

Model Indoor Unit

Model Outdoor Unit

Operation

RAP Valve Kit

3-Way Control PCB

3-Way Valve Kit
(Single SVK)

3-Way Valve Kit
Multiple Connection Port Type 4 Ports
(Multiple SVK)

Distribution Joint Kit
(2-Way)

Distribution Joint Kit
(3-Way)

CZ-P160RVK2

CZ-CAPE2

CZ-P160HR3

CZ-P4160HR3
(160 Type x 4)

Solenoid Valve Relay Kit
(Accessary Parts)

CZ-P160BK2
for 22.4 kW or less

 

CZ-P680BK2
for more than 22.4 kW

CZ-P224BH2
for 22.4 kW or less

 

CZ-P680BH2
for more than 22.4 kW

E2 Type
High Static Ducted
・ S-180ME2E5
・ S-224ME2E5
・ S-280ME2E5

2-Way ME1, ME2, MS3

Cooling Only

-

-

-

-

-

-

-

2-Way ME1&ME2

Cooling or Heating

-

-

-

-

-

-

-

E2 Type
High Fresh Air Ducted
・ S-224ME2E5
・ S-280ME2E5

2-Way ME1, ME2, MS3

Cooling Only

-

-

-

-

-

-

-

2-Way ME1&ME2

Cooling or Heating

2 pcs

2 pcs

-

-

-

2 pcs

-

*Valve Kit is not required for cooling only system. For the details on the information, please consult an authorised dealer.