Retail Sales Price: Panasonic Online Price: SHOP NOW Buy from Panasonic Where to Buy Out of Stock at Panasonic Online false false false

Human Detection Sensor for ECONAVI

CZ-CENSC1

ECONAVI Sensor for Optimum Energy- Saving Operations

ECONAVI Sensor detects the presence or absence of people and the level of activity in each area of an office. When unnecessary heating or cooling is detected, indoor units are individually controlled to match office conditions for energy-saving operation.
  • ECONAVI
Zoom In
Zoom Out
Close

Specs

CZ-CENSC1

Photo of CZ-CENSC1
  • ECONAVIECONAVI

Detects human activity and adjusts temperature by 2 degrees (up or down) to optimise comfort and efficiency.

If there is no activity detected for a set time period, the Econavi will stop the unit or move to a new temperature previously set.

The ECONAVI device is installed independently of the indoor unit, and is located in the area best suited for detection.

Energy saving in office: If the air conditioning is left on after the last employee leaves the office, ECONAVI will automatically react.

Increased comfort in hotel rooms: When presence is detected in the room, the temperature is automatically adjusted.

CZ-CENSC1
Dimensions (mm) (H) 120 x (W) 70 x (D) 32
Weight 75 g
Temperature/Humidity range 0 ℃to 40℃/20% to 80% (No condensation)
* Indoor use only.
Power source DC16V (Supplied from indoor unit)
Connections 1 sensor per indoor group

Documents

Combination

Features

Connectable with Various Types of FSV Indoor Units

The ECONAVI sensor can be connected with various types of indoor units by setting it remotely to maximize the detection area. Installation flexibility ready for indoor unit replacement and layout changes.
[Compatible indoor units] 1)4-Way Cassette 2)Mini Cassette 3) Wall-Mounted 4)Twenty Series Duct 5)Mid Static Duct 6)Ceiling
Connectable with Various Types of FSV Indoor Units

Human Activity and Presence Detection

In the Morning

Thorough cooling when there is a high level of activity.
In the Morning

In the Afternoon

Reduced cooling when there are fewer people.
In the Afternoon

At Night

Automatic Thermo Off depending on conditions at the end of the day.
At Night

Activity / Presence Detection

Activity Detection

Presence Detection

Higher activity

 Lower activity

Short time absence

 Long time absence

Cooling Set Temp.

No change

+1 °C

+2 °C

Cooling Thermo OFF / Stop

Heating Set Temp.

-1 °C

No change

 -2 °C

 Heating Thermo OFF / Stop

Detection Interval

Every 2 minutes

After 20 minutes absence

 After 3 hours absence

Flexible Installation Realizing Wide Detection Area

The sensor can be installed flexibly avoiding pillars, walls, and other office equipment that obstruct the sensor. This enables accurate sensing to save energy.
A) Wide detection area. B) Dead zone.
1)A sensor is remotely set to maximise the detection area. Installation flexibility ready for indoor unit replacement and layout changes.
Flexible Installation Realizing Wide Detection Area