Retail Sales Price: Panasonic Online Price: SHOP NOW Buy from Panasonic Where to Buy Out of Stock at Panasonic Online false false false

Energy Recover Ventilator

SHOP NOW

ERV Standard Series

24-hour Continuous Ventilation

Continuous 24-hour ventilation brings fresh air into the house and expels stale air. An Energy Recovery Ventilator minimises air conditioning energy-loss, creating a highly efficient and energy-saving ventilation environment.
Zoom In
Zoom Out
Close

Features

Integrated Air Supply/Exhaust

It can both supply and exhaust air, and it fits neatly in the ceiling and does not interfere with accessories.
Integrated Air Supply/Exhaust

Energy Saving

Highly efficient energy recovery reduces energy loss during ventilation, saving energy. (Example: FY-150ZDY8)
Energy Saving

Takes Up Less Ciling Space

A counter-flow heat-exchange element has been used to reduce both noise and size/profile. The device is slim and easy to install.
Takes Up Less Ciling Space

Specs

FY-150ZDY8M

Photo of FY-150ZDY8M

FY-250ZDY8M

Photo of FY-250ZDY8M

FY-350ZDY8M

Photo of FY-350ZDY8M

FY-500ZDY8M

Photo of FY-500ZDY8M

FY-650ZDY8M

Photo of FY-650ZDY8M

FY-800ZDY8M

Photo of FY-800ZDY8M

FY-01KZDY8A

Photo of FY-01KZDY8A

Counter-flow heat-exchange element used
for reduced noise and more compact body.

All maintenance can be performed via a single inspection hole.

Straight air supply/exhaust system used for easier installation.

Each unit can be mounted in reverse position.

Equipped with an Extra-High setting.

Can incorporate a medium-performance filter
(optional, installed at site).

FY-150ZDY8M FY-250ZDY8M FY-350ZDY8M FY-500ZDY8M FY-650ZDY8M FY-800ZDY8M FY-01KZDY8A
Input [W] ExHi/Hi/Lo 114/107/77 128/123/96 190/185/175 289/228/185 347/295/210 418/378/295 464/432/311
Current [A] ExHi/Hi/Lo 0.48/0.45/0.32 0.53/0.51/0.41 0.83/0.81/0.79 1.21/0.94/0.77 1.48/1.23/0.91 1.76/1.64/1.33 1.99/1.89/1.37
Air Volume [m³/h] ExHi/Hi/Lo 150/150/120 250/250/190 350/350/240 500/500/440 650/650/460 800/800/630 1000/1000/700
External Static Pressure [Pa] ExHi/Hi/Lo 80/70/25 105/95/45 140/60/45 120/60/35 65/40/40 140/110/55 105/80/75
Temperature Exchange Efficiency (%) ExHi/Hi/Lo 75/75/77 75/75/77 75/75/78 75/75/76 75/75/79 75/75/76 75/75/79
Noise [dB] ExHi/Hi/Lo 29/29/21.5 31.5/30.5/26.5 33.0/31.0/25.5 36.5-37.5 37.5/35.5/32.0 37.5/37.0/34.5 38.5/37.5/34.5
Product Weight [kg] 25 29 49 57 68 71 83

Documents

Combination