$ #,###.00 000 010 //panasonic-newzealand.ibrandiq.com/en/Widgets/FluidPanNZ/{0} //panasonic-newzealand.ibrandiq.com/Products/MultipleInStock/FluidPanNZ/{0}
Photo of 7.1kW Reverse Cycle InverterMid-static Ducted Air Conditioner

7.1kW Reverse Cycle Inverter
Mid-static Ducted Air Conditioner

GENERAL Type of Split System Air Conditioner Ducted
Indoor Unit S-71PF1R5A
Outdoor Unit U-71PE1R5A
Inverter Equipped Yes
Function Cooling + Heating
PERFORMANCE Electrical Voltage (V) 240
Phase 1
Cooling Capacity (kW) 7.1
Cooling Capacity Range - Min ~ Max (kW) 2.5 ~ 8.0
Heating Capacity (kW) 8.0
Heating Capacity Range - Min ~ Max (kW) 2.0 ~ 9.0
EER (w/w) 3.84
COP (w/w) 3.85
Total Power Input - Cooling / Heating (kW) 1.85 / 2.08
Cooling Operating Temperature Range (˚C) -15 ~ 46
Heating Operating Temperature Range (˚C) -20 ~ 24
Compressor Type Inverter
Refrigerant Type R410A
SPECIFICATIONS No. of Indoor Units 1
Indoor Unit Dimensions W x H x D (mm) 1000 x 290 x 700
Outdoor Unit Dimensions W x H x D (mm) 940 x 996 x 340
Net Weight - Indoor Unit (kg) 33
Net Weight - Outdoor Unit (kg) 69
Air Volume - Indoor - Cooling (L/s) 350
Air Volume - Indoor - Heating (L/s) 350
Air Volume - Outdoor - Cool / Heat (L/s) 1000 / 1000
External Static Pressure (Pa) 70 (10 ~ 150)
Sound Pressure Level - Indoor - Cooling- H / M / L (dB(A)) 35 / 32 / 26
Sound Pressure Level - Indoor - Heating- H / M / L (dB(A)) 35 / 32 / 26
Sound Power Level - Indoor - Cooling - H / M / L (dB(A)) 58 / 55 / 49
Sound Power Level - Indoor - Heating - H / M / L (dB(A)) 58 / 55 / 49
Sound Pressure Level - Outdoor - Cooling / Heating (dB(A)) 48 / 50
Sound Power Level - Outdoor - Cooling / Heating (dB(A)) 65 / 67
Pipe Length - min. ~ max. (m) 5 ~ 50
Elevation Difference - Outdoor Located Lower, Outdoor Located Higher (m) 15 , 30
Maximum Chargeless Length (m) 30
Piping Connections - Liquid / Gas (mm) Ø9.52 / Ø15.88
Warranty 5 Years Manufacturer's Warranty
FEATURES Drain Piping (mm) Up to 702
Remote Control Wired / Wireless Optional
Programmable Timer Yes